Free Eyewash Station Inspection Checklist for Excel
A weekly checklist for each eyewash, eye/face wash, combination shower or portable unit, plus the log and register behind it: a station that fails stays DO NOT USE until it is repaired, and weekly checks, annual inspections and fluid changes show OVERDUE or DUE SOON. Works in Microsoft Excel and Google Sheets.

What an eyewash station inspection covers
An emergency eyewash is only useful if it works the first time, within seconds, with clean water. Workplace safety rules require eyewash facilities wherever eyes can be splashed with corrosive materials, and the industry standard sets the routine: plumbed units are activated every week, so the water sitting in the pipe is flushed out, and every unit gets a full inspection once a year. Portable self-contained units are checked weekly and their flushing fluid is replaced on the maker's schedule.
The Weekly Checklist prints one sheet per station per month, a column per week:
- Access and signage: a clear path, the station within about 10 seconds of the hazard, a visible sign and good light.
- Station: dust caps that pop off, a valve that opens in a second and stays open hands-free, water that runs clear, flow from both nozzles, tepid water, a clean bowl and drain, no leaks.
- Portable units: the fluid full and sealed, and within its replacement date.
- Records: the inspection tag signed and dated.
A signed tag shows someone flushed it. It cannot stop a crew from relying on a station whose water came out brown. So the workbook keeps the record behind it:
Inspection Log. One row per weekly check, annual inspection, fluid change or repair, with PASS or FAIL. A FAIL stays an OPEN DEFECT until the repair date is entered.
Station Register. One row per station, with type, location, make and model, serial number and water supply. It reads the log, shows DO NOT USE while a defect is open, and runs three clocks: the weekly check, the annual inspection, and, for portable types only, the fluid change interval from the Station Types tab (24 months for sealed cartridges, 3 for gravity tanks, both editable). Status reads OVERDUE when any of them runs out, DUE SOON just before, and IN SERVICE otherwise.
For the rest of your emergency equipment, use the fire extinguisher inspection checklist.
Who uses an eyewash station inspection checklist
Wherever chemicals, dust or battery acid can reach someone's eyes.
Laboratories
Eyewash and combination showers in teaching and research labs.
Manufacturing plants
Stations at chemical dosing, plating and paint lines.
Warehouses
Battery charging areas for forklifts and pallet trucks.
Auto shops
Battery, brake fluid and parts-washer areas.
Hospitals and clinics
Disinfectant rooms, labs and sterile processing.
Facilities teams
The weekly round across every station on site, and the annual inspection.
Before you fill it in
The tag says flushed on Friday. Nobody wrote down the water was brown.
Try UNIO24 to automate eyewash station inspections.
Try UNIO24 FreeA spreadsheet goes out of date within days, and keeping it current takes someone's time every week. UNIO24 automates that work: each check, defect and repair updates the station's record as it happens.


| Capability | Free Template | UNIO24 FreeRecommended for multi-site teams |
|---|---|---|
| Inspections | ||
| Weekly eyewash checklistThe template prints a monthly sheet per station. UNIO24 runs your checklist on a phone at the station. | Partial | Yes |
| Photos of the problemThe rusty water or the missing dust cap, attached to the check. | No | Yes |
| Defects and due dates | ||
| Keep a failed station flaggedThe register shows DO NOT USE from the log. UNIO24 records the defect and can turn it into a repair work order. | Partial | Yes |
| Weekly, annual and fluid change datesBoth track them. UNIO24 also schedules the next inspection. | Partial | Yes |
| Data & reliability | ||
| Many inspectors and buildings at onceA shared file gets overwritten. UNIO24 handles simultaneous users. | Partial | Yes |
| Full history per stationEvery check, defect, repair and fluid change kept on the station | Partial | Yes |
| Full support | 0/ 6 | 6/ 6 |
Frequently Asked Questions
About eyewash inspections and the template
Is the eyewash station inspection checklist free?
Yes. No cost, no subscription, no card. Enter your name and email and the Excel file downloads instantly.
How long should you flush an eyewash station during the weekly check?
Long enough for the water to run clear. Many programs use 3 minutes as the standard, longer if the water stays cloudy or rusty. If it does not clear, tag the station Do Not Use, tell people where the nearest working station is, and have the supply checked.
Do portable eyewash stations need weekly checks?
They are not activated weekly like plumbed units, but they still need a weekly look: the fluid full and sealed, the unit within its replacement date, the cover in place and the access clear. Replace the fluid or cartridge by the date the maker gives. In the template, set the months per portable type on the Station Types tab.
How often should an eyewash station be inspected?
Plumbed units are activated weekly to flush the line and confirm they work, and every unit gets a full inspection once a year. Portable self-contained units are checked weekly too, and their flushing fluid is replaced on the schedule in the maker's manual. The template runs all three clocks per station.
What should the water temperature be?
Tepid: comfortably warm, roughly between 60 and 100 °F (16 to 38 °C). Cold water makes people stop flushing too early, and hot water can make a chemical injury worse. Stations on a cold supply in an unheated space often need a tempering valve.
Are eye wash bottles enough?
Personal wash bottles are a supplement for the first seconds while someone gets to a station. They do not replace an eyewash station that delivers a steady flow for 15 minutes, and a drench hose on its own does not either.